132KV transmissielyn Gegalvaniseerde staal rooster toring Detailing en beraming

transmissielyn Gegalvaniseerde staal rooster toring

Shop Detailing en beraming

Before leaving the Manufacturer’s Works all tower members shall be hard stamped with distinguishing numbers and/or letters corresponding to distinguishing numbers and/or letters on approved drawings or material lists to be submitted by the Contractor. The erection marks shall be located on the member so that, nadat vergadering en oprigting, all members can be individually identified.

The erection marks shall be stamped before galvanizing and shall be clearly legible after galvanizing. Care shall be taken to distinguish between various grades of steel.

Die oprigting punte sal die standaard toring naam inkorporeer soos gegee in klousule B1.5.9.

The erection marks shall also incorporate nomenclature to identify all members with increased galvanizing thickness as detailed in Clause B1.5.5.1

All tower connections shall be bolted unless otherwise specified.

indien moontlik, twee bout gate moet voorsien aan die een kant van al skuins verspanning en by al die ander punte waar dit nodig mag wees om lede dryf in plek.

Verbindings sal die maksimum spanning in lede te ontwikkel met geen krediet gegee vir aangrensende gewrigte. Waar skoot verbindings word gebruik, die toelaatbare ontwerp spanning sal verminder word deur 30 persent. Die aantal verbindings sal die minimum uitvoerbaar wees.

Eksentrisiteit van verbindings sal verminder word tot die minste uitvoerbaar waarde. Alle web lede sal wees in een stuk waar prakties moontlik en al dubbel-skuins lede web-stelsel by hul snypunt sal verbind word deur ten minste een bout.

 

1. Produk Naam: krag transmissie toring / kommunikasie toring
2. Plek van oorsprong: Hengshui, Sjina (vasteland)
3. toring Tipe: engel staaltoring
4. toring Gebruik: kommunikasie toring, Beligting stok toring, Radio en televisie toring, substasie argitektuur, telekommunikasie-toring
5. Standard: GB ANSI DIN ISO JIS
6. materiaal: Gewoonlik Q345B / A572, minimum opbrengs krag>= 345n / mm2, Q235B / A36, minimum opbrengs krag>= 235n / mm2, Asook Hot gerol spoel uit Q460 ,ASTM573 GR65, GR50 ,SS400, SS490, om ST5
7. ontwerp Hoogte: 20-80m
8. Oppervlak behandeling: Hot-gedoop-gegalvaniseerde volgende ASTM A123, of enige ander standaard as wat nodig is
9. verband af: Bolt verband&sweiswerk
10. Kenspanning Range: 10KV-1000KV
11. sertifisering: EG, SGS, IAF, CNAs, ISO9001:2015, ISO14001:2004, OHSAS18001:2007
12.produseer Style: Vervaardig volgens behoeftes van die kliënt se tekeninge of ontwerp.

staal rooster gegalvaniseerde hoogspanning transmissie torings
gaatjieslepel hoekyster, gegalvaniseerde hoek bar 5mm, aluminiumhoekyster, dompel opzweren hoek, geperforeerde hoekyster, staal gegalvaniseerde hoekyster, hoekyster, warm gegalvaniseerde hoek staal, 45 graad hoekyster

Stressed members shall be properly reinforced where the outstanding leg is blocked out.

All members that have an angle up to 30 jy. met die horisontale versigtig moet gedetailleerde om te verseker dat personeel sal nie permanent verwring hulle. 'N Las van 150 kg sal oorweeg word vir die konstruksie of instandhouding personeel.

Splices in the legs of towers or extensions shall be located immediately above horizontal members, Indien moontlik, of hoër diagonale stut verbindings.

The heel of the inside angle of splice angle shall be ground to fit the fillet of the outside angle. Tower members shall have flat surfaces up when practicable.

Plates or other approved means of attaching conductor insulators, skild draad hardeware en verspringer isolators moet voorsien.

Special holes shall be provided for anti-climbing devices, gevaartekens, toring aantal tekens en toring grou verbindings in ooreenstemming met die tekeninge.

All members carrying tension only shall be detailed shorter than the theoretically calculated length. lede 3 m of minder in lengte moet gedetailleerde 3 mm korter.

Unspliced members more than 3 m in lengte moet kort wees uiteengesit deur 'n bedrag gelykstaande aan 1.5 mm vir elke 3 m van lengte of groot gedeelte daarvan plus 1.5 mm, met 'n maksimum van 6 mm.

For tension only spliced members, die bedrag van trekking bereken soos hierbo beskryf vir die algehele lengte moet verhoog word deur 'n bykomende 1.5 mm.

Die winkel besonderhede sal die bedrag waarmee elke lid is verkort dui.

The Contractor shall pay particular attention to ensuring that all long members are of sufficient section so that after punching they will withstand ordinary rough handling during further fabrication, verskeping, los en oprigting.

The spacing of bolts, van verskillende groottes, die rand afstande en die minimum groottes van hoeke is soos volg (al uitgespreek in mm):

Diameter of the bolts 12 14 16 20 22 24 27 30

– Afstand na die cut-rand in die rigting

of the load 20 23 25 30 35 40 45 50

– Afstand na die cut-rand in die rigting van

the load for splices and hangers of the

cross beam 25 30 35 40 45 50 55 65

– Afstand na die rand loodreg op die

direction of the load 16 18 20 25 27 30 34 38

Distance between holes 35 40 44 54 59 64 70 80

Minimum width of the leg of the angle 35 40 45 60 65 70 75 80

Die afstande na die cut-rand en gerol-rand en tussen gate gemeet vanaf die middel van die gat.

waar prakties moontlik, die spasiëring moet nie minder nie as drie bout diameters. Rand afstande hierbo gespesifiseer word nie verminder deur onder run as gevolg van rollende toleransies.

waar moontlik, boute moet so geleë wees dat 'n socket wrench gebruik kan word om die grendel te trek.

Plat ringe sal oor die algemeen in ooreenstemming met BS 4320 van die volgende dikte:-

– 12 en 14 mm bolts washers 2.5 mm dik

– 16 en 20 mm bolts washers 3.0 mm dik

– 24 en 30 mm bolts washers 4 0 mm dik.