B1.5.3     Sizing of Tower Members

 

Member and member connection design sizing shall be performed in accordance with the latest issue of Guide for Design of Lattice Steel Transmission Structures, ANSI/ASCE 10-97.

            All tower members shall be sized using the member loads indicated on the tower calculation sheets to be submitted for approval. The bending moments (if any) of the tower members shall also be taken into consideration for member sizing.

            The most efficient grades of steel and structural sections available shall be used to yield the lowest in‑place tower cost. The type and grade of steel shall conform to the latest applicable standards, specifications and recommended practices of the industry.

            All tension members shall be designed to the full minimum yield point of the material.

            Shear and bearing stress on bolts shall be computed using the nominal diameter of the bolt.  Tensile stress on bolts shall be computed on net area of the bolt.  The limit stresses in the design of bolts and nuts shall be subject to the Engineer’s approval.

           The Contractor shall be responsible for ensur­ing that the towers are capable of withstanding the member stresses without permanent deformation in any parts of the tower.

 

The maximum ratio of effective unsupported length of steel members to the relevant radius of gyration (L/R) shall not exceed:-

  1. a) Leg members and cross arms chords:                120
  2. b) All other members carrying calculated stresses:              200
  3. c) Redundant members:                                          250
  4. d) Cross arm hanger:                                        300
  5. e) All other tension‑only members:                          350

The thickness of tower members shall not be less than:

  1. a) Legs and main members of cross arm:                     6 mm
  2. b) All other loaded members:                                   5 mm
  3. c) Redundant members:                                          4 mm
  4. d) Steel below ground:                                      6 mm
  5. e) Gusset plates: thickness of member connected        plus 2 mm
  6. f) Minimum bolt diameter for leg members:                  16 mm

The sizes of the angles used for tower members shall not be less than:

  1. a) Leg members:                                 50 x 50 x 6 mm
  2. b) All other loaded members:                     40 x 40 x 5 mm
  3. c) Redundant members:                            35 x 35 x 4 mm

            The maximum width of angle leg shall not exceed 16 times the thickness.

            Flat bars and rods shall not be used for tower members.

            The angle between any two members, which are connected to each other, shall not be less than 13o.

            A maximum of three bolt diameters may be used for anyone tower type. All bolts of the same diameter used on more than one tower type, shall be of the same strength in order to avoid errors during erection. Bolts shall be provided with flat washers. Lock washers are not required as bolt threads will be punched to prevent loosening or theft.  All bolts shall be supplied in sufficient quantities to allow for normal construction losses.

            To allow for maintenance, all members that have an angle up to 300 with the horizontal shall be designed to resist a point load of 150 kg.

 

 

Self-Supporting steel lattice Towers for electric transmission line Design

  

Structure Steel

2. Grade

Mild Steel

High Tensile Steel

GB/T 700:Q235B, Q235C,Q235D

GB/T1591:Q345B, Q345C,Q3455D

ASTM A36

ASTM A572 Gr50

EN10025: S235JR, S235J0,S235J2

EN10025: S355JR, S355J0,S355J2

3. Design Wind Speed

Up to 250 km/h

4. Allowable deflection

0.5 ~1.0 degree @ operational speed

5. Tension strength (Mpa)

360~510

470~630

6. Yield strength (t≤16mm) (Mpa)

355

235

7. Elongation (%)

20

24

8. Impact strength KV (J)

27(20°C)—Q235B(S235JR)

27(20°C)—Q345B(S355JR)

27(0°C)—Q235C(S235J0)

27(0°C)—Q345C(S355J0)

27(-20°C)—Q235D(S235J2)

27(-20°C)—Q345D(S355J2)

Bolts & Nuts

9. Grade

Grade 4.8, 6.8, 8.8

10. Standards for mechanical properties

10.1 Bolts

ISO 898-1

10.2 Nuts

ISO 898-2

10.3 Washers

ISO 6507-1

11. Standards for Dimensions

11.1 Bolts

DIN7990, DIN931, DIN933

11.2 Nuts

ISO4032, ISO4034

11.3 Washers

DIN7989, DIN127B, ISO7091

Welding

12. Method

CO2 Shielded Arc Welding & Submerged Arc Welding(SAW)

13. Standard

AWS D1.1

Marking

14. Method of marking of the members

Hydraulic Press Stamping

Galvanizing

15. Galvanization standard of steel sections

ISO 1461 or ASTM A123

16. Galvanization standard of bolts and nuts

ISO 1461 or ASTM A153

Test

17. Factory test

Tensile test,Elements analysis, Sharpy test(impact test), Cold Bending, 

 Preece test,Hammer test

Capacity

18. Maximum Production Capacity 

50,000 TON per annum



 


B1.5.1     Conductor Spacing and Clearances

           The crossbeam arrangement and the dimensions shown on the tower outline drawings shall be assumed as the minimum requirements. It is the Contractor’s responsibility to supply cross beam extensions and insulator string linkages to ensure that minimum clearances are maintained.

            The towers shall be designed to comply with the minimum net clearances between earthed metal and live conductor or fitting shown on the tower drawings.

            The specified clearances between line conductors and all supporting steelworks shall be obtained on the assumption that the conductor Self supporting tower for electric transmission line

may attain a position at any angle between 10o above and 20o below the horizontal for all types of tower. The down-leads on terminal towers shall be assumed to exit from tower at any horizontal angle in between 0º and 45º, from the longitudinal centerline at any vertical angle in between 0º and 45º.

 

The minimum clearances between the conductor at the maximum sag, at 75oC conductor temperature in still air, and ground or other objects shall be as follows:

Obstacles

230 kV

66 kV

Normal ground and secondary roads

8.0 m

6.5 m

Main roads, highways and railways

9

7

Buildings

not permitted

not permitted

Power supply circuits up to 400 KV

5

4

Telecommunication lines 

5.25 m

4.6 m

Railways     

12.5 m

10.5 m

 